Commercial
P35 Pump Station
OH 1 – OH 2 – OH 3 – OH4 + FM5560 applications.
Technical Data
- Outlet pressure: 100 – 130 bar
- Inlet water ¬ow: 56 litres/min at 2 bar
- Flow: 35 – 50 litres/min
- Power consumption: 11kw
- Voltage supply: 3 x 400 VAC 50Hz (3 x 220 VAC 50Hz)
* For inlet water pressure between 0.7 – 2 bar an extra strainer shall be installed with 25 micron litre prior to pump inlet.
Features
- Flow: For 100 bar system, up to 50 litres/min.
- Electric driven piston high pressure pump with frequency-controlled rpm on motor with adjustable system pressure for small systems.
- Easy to install, access, operate and maintain.
- Strainer 50 micron, safety valve, pressure gauge, pressure transmitter and test outlet under the same hood.